Explosion-Proof Buttons
KVE-2 explosion-proof contact blocks are intended for use in low-voltage electrical circuits in combination with explosion-proof enclosures, for indoor or outdoor installation, as well as on offshore platforms and port terminals, in hazardous areas with explosive atmospheres or combustible dust.
Technical Parameters of the KVE-2 Series
| № | Parameter | Value |
| KVE-2 | ||
| 1 | Enclosure Protection Rating (IP) according to GOST 14254-2015 | |
| 1,1 | not installed in the enclosure | IP 20 |
| 1,2 | installed in the enclosure | IP 67 |
| 2 | Operating Temperature, °C: | from -60 to +60 |
| 2.1 | Relative Humidity | 100% at +25°C |
| 3 | Explosion Protection Markings: | |
| 3,1 | Gas Markings: | Ex d e IIC Gb U |
| 3 | Dust Markings: | Ex tb IIIC Db U |
| 4 | Rated Operating Voltage, Ue, V | 12-380 |
| 5 | Rated Current, In, A (AC) | 10 |
| 6 | Frequency of Operations, Cycles/Hour | 3600 |
| 7 | Mechanical Durability, Cycles | 1х106 |
| 8 | Cable Cross-Section, mm2 | 0,75….1,5 |
| 9 | Dimensions | KVE-2: 84×45.5×39; KVE-2-mushroom head: 103×45.5×40 |
| 10 | Weight | KVE-2 – 79 g KVE-2-mushroom head – 125 g |






KVE Series 2
For Explosion-Proof Contact Blocks:
KVE – Х1 – Х2Х3 –(wХ4)– Х5 – Х6-Х7-Х8 –Х9 … where
Х1 – series number 2
X2 X3 – type of contact configuration:
1 – normally open,
2 – normally closed;
Possible combinations: 21, 11, and 22.
w (optional) – the symbol is added when ordering a KVE unit with a pre-installed cable;
X4 (optional) – the symbol indicates the cable length in meters when ordering a KVE
with a non-standard cable length (different from 1 m);
X5 – voltage:
AC/DC12
AC/DC24-36
AC/DC110
AC220-380
AC/DC220
X6 – control type:
1 – momentary pushbutton;
2 – double pushbutton;
3 – mushroom-head latching pushbutton;
4 – mushroom-head latching pushbutton with key;
Х7 – text (by default, printed on an adhesive thermal label; for individual orders — on a stainless steel nameplate):
1 – (none)
2 – on
3 – off
4 – start
5 – stop
6 – auto
7 – manual
8 – fault
Other inscriptions available upon request.
X8 – colour:
1 – white;
2 – red;
3 – green;
4 – yellow;
5 – blue;
6 – black;
X9 – illumination:
0 – none;
1 – available (only for momentary pushbuttons)
* If any position such as X1, X2, etc., is not required, use “0”. If several positions at the end of the code (e.g., “options”) are not required, simply finish the code.
Explosion-Proof Cable Glands
Explosion-Proof Control Stations
Explosion-Proof Junction Boxes
Explosion-Proof Cabinets
Explosion-Proof Luminaires
Explosion-Proof and Industrial Enclosures
Explosion-Proof Controls