Explosion-Proof Switching Module
Explosion-proof switching modules (circuit breakers, switch disconnectors, cam switches) are designed for controlling and protecting electrical circuits against overloads and short circuits, as well as for switching, protective disconnection, and circuit selection. They are used in the chemical, petrochemical, pharmaceutical, and other industries where explosion-proof equipment is required.
Technical Specifications
| Explosion Protection Markings: | |
| Gas Markings: | 1Ex db IIB + H2 T6…T3 Gb X; 1Ex db IIC T6…T3 X 1Ex db IIC T6…T3 X (except acetylene) 1Ex db IIC T6…T3 Gb X (except acetylene) 1Ex db IIC T6…T4 X (except acetylene) 1Ex db IIC T6 X (except acetylene) 1Ex db IIC T6 Gb X (except acetylene) |
| Dust Markings: | Ex t b IIIC T100°C Db |
| Ingress Protection: | IP65/66 |
| Rated Voltage: | up to 990 V |
| Rated Current: | up to 800 A |
| Permissible Ambient Temperature: | from -60 to +80ºС |
| Climatic Design: | NF4, MU4, NF5, T1, T2, T3, T5, W4, M4, U4, U5, F5, N5, TH1, TH2, TH3, TH5, TA1, TA2, TA3, TA5, МT1, MT2, MT3, MT5, MU5, MU3 |
| Material: | low-copper aluminium |
| Default Colour: | light-grey RAL 7005, can be supplied in any colour upon request |
The equipment configuration, including terminals, cable glands, circuit breakers, and safety disconnectors, is agreed with the customer under separate orders.
The equipment is manufactured in the following climatic versions and placement categories: NF4, MU4, NF5, T1, T2, T3, T5, W4, M4, U4, U5, F5, N5, TH1, TH2, TH3, TH5, TA1, TA2, TA3, TA5, МT1, MT2, MT3, MT5, MU5, MU3.1 according to GOST 15150-69.
|
Switching Module Name |
||||||||||||||||
|
Technical |
MK.16 |
MK.20 |
MK.25 |
MK.32 |
MK.40 |
MK.63 |
MK.80 |
MK.12u |
MK.100 |
MK.125 |
MK.160 |
MK.250 |
MK.315 |
MK.400 |
MK.630 |
MK.800 |
|
Explosion Protection Markings |
1Ex db IIB + H2 T6…T3 Gb X; 1Ex db IIC T6…T3 X 1Ex db IIC T6…T3 X (except acetylene) 1Ex db IIC T6…T3 Gb X (except acetylene) 1Ex db IIC T6…T4 X (except acetylene) 1Ex db IIC T6 X (except acetylene) 1Ex db IIC T6 Gb X (except acetylene) |
|||||||||||||||
|
Rated Operating AC voltage, V |
415 \ 690 |
|||||||||||||||
|
Rated Impulse Withstand Voltage, kV |
8 |
12 |
||||||||||||||
|
Rated Operating Current, A (AC-21, 415V) |
16 |
20 |
25 |
32 |
40 |
63 |
80 |
125 |
100 |
125 |
160 |
250 |
315 |
400 |
630 |
800 |
|
Rated Operating Current, A (AC-23, 690V) |
16 |
20 |
25 |
25 |
25 |
40 |
40 |
63 |
63 |
63 |
160 |
250 |
315 |
400 |
630 |
800 |
|
Rated Operating Power, kW at 415V (AC -23) |
7,5 |
9 |
11 |
15 |
18,5 |
30 |
37 |
55 |
45 |
55 |
72 |
112 |
142 |
180 |
284 |
360 |
|
Rated Operating Power, kW at 690V (AC -23) |
7,5 |
11 |
15 |
15 |
18,5 |
30 |
37 |
55 |
45 |
55 |
123 |
193 |
244 |
310 |
488 |
621 |
|
Maximum Cross-Section of Main Cable Cores, sq. mm (Flexible/Rigid) |
0.75/10 |
0.75/10 |
0.75/10 |
0.75/10 |
0.75/10 |
2,5/35 |
2,5/35 |
70 |
70 |
70 |
70 |
120 |
185 |
240 |
240 |
240 |
|
Cross-Section of Additional Cable Cores, mm |
0,75..2,5 |
|||||||||||||||
|
Overall Dimensions of the Boxes and Cabinets (ShV series) without Cable Glands, mm (L x W x D) |
ShV-1-17b dimensions 175x175x133 mm. |
ShV-1-17b dimensions 284х184х120 mm. |
ShV-1-17b dimensions 306х206х206 mm. |
ShV-1-17b dimensions 575х395х266 mm. |
||||||||||||
|
Protection Rating (IP) according to GOST 14254-2015 |
IP66 |
|||||||||||||||
|
Ambient temperature, ºС |
-60 to 60 |
|||||||||||||||
Explosion-Proof Cable Glands
Explosion-Proof Control Stations
Explosion-Proof Junction Boxes
Explosion-Proof Cabinets
Explosion-Proof Luminaires
Explosion-Proof and Industrial Enclosures
Explosion-Proof Controls