SVVKGm Explosion-Proof Cable Glands for Heating Cables in Flexible Metallic Conduit
SVVKGm explosion-proof cable glands are intended for the entry of non-armoured heating cables in flexible metallic conduit in the enclosures of explosion-proof electrical equipment installed indoors or outdoors, as well as on offshore platforms and port terminals, in hazardous areas with explosive atmospheres or combustible dust.
Technical Specifications
| Explosion Protection Markings: | |
| Gas Markings: | 1ExdIICGb X, 1ExeIIGb X, 2ExnRIICGc X |
| Dust Markings: | ExtaIIICDa X |
| Ingress Protection: | IP 66/67/68 |
| Permissible Ambient Temperature: | -60….+130 С -80….+250 С (special design) |
| Gland Material | Nickel-plated brass (by default) Stainless steel (-N) Aluminium (-А) |
| Sealing Ring Material | Silicone |
| Sealing Type | Compression dynamic seal |
|
Code |
Thread Type M |
Thread Type G, K (Optional) |
Cable Ø, mm |
Flexible Metallic Conduit Diameter |
Type of Flexible Metallic Conduit* |
Across Flats Sw |
Total Length TL |
Thread Length L, mm for M / G / NPT Types |
|
SVVKgm-20m (MR15) ShG |
M20 |
1/2” |
9х5-12х8 |
5,9/9 |
RZ TsKh 15 MRPI 15, GERDA-MG-15, GERDA-MG-16 |
27 |
59 |
15 / 16 /17 |
|
SVVKgm-20 (MR15) ShG |
7,8/12,5 |
|||||||
|
SVVKgm-20 (MR18) ShG |
9,1/15 |
RZ TsKh 18 MRPI 18 |
||||||
|
SVVKgm-20 (MR20) ShG |
10,9/18 |
RZ TsKh 20 MRPI 20, RZ TsKh 22 MRPI 22, GERDA-MG-22, GERDA-MG-22 |
*Cable glands for other cable and armour diameters, as well as with alternative thread types, are available on request.

Х1 VVK Х2 – Х3 – Х4 – Х5 where
|
С |
VVKg |
m |
N |
20 |
M20х1.5 |
|
Х1 |
Х2 |
Х3 |
Х4 |
Х5 |
Here:
X1 – entering cable type (conduit connection (C);
VVK – product designation: "VVK" – explosion-proof cable glands;
Х2 – type of cable gland sealing ring (m – one special elastic ring suitable for the entire cable diameter range)
Х3 – gland material: nickel-plated brass (default, no marking), N – stainless steel, L – bare brass, S – steel, SO – galvanized steel, A – aluminium. Similar materials may also be used;
Х4 – cable gland size;
Х5 – entry thread (metric thread M is indicated by default);