TAVVKu Explosion-Proof Cable Glands for Armoured Cables in Flexible Metallic Conduit or Conduit Connection

TAVVKu explosion-proof cable glands are intended for the entry of armoured cables in conduit connection in the enclosures of explosion-proof electrical equipment installed indoors or outdoors, as well as on offshore platforms and port terminals, in hazardous areas with explosive atmospheres or combustible dust.

Order

Technical Specifications

Explosion Protection Markings: 
Gas Markings:1Ex d IIC Gb X, 1Ex e II Gb X, 2Ex nR IIC Gc X
Dust Markings:Ex ta IIIC Da X
Ingress Protection:IP66/67/68
Permissible Ambient Temperature:-60 to +130ºС
Climatic Design:NF1 by default; other options (MU1, U1, W1) on request
Material:nickel-plated brass, plain brass, aluminium, stainless steel.

Code

Thread Type M

Thread Type G, K (Optional)

Inner Thread Type (D1)

Inner Cable Ø, mm

Outer Cable Ø, mm

Across Flats Sw

Total Length TL

Thread Length L, mm for M / G / NPT Types

TAVVKu-16

M16

3/8″

G3/8

4-10

5-13

24

81

15 / 16 / 17

TAVVKu-16/u

M16

3/8″

G1/2

4-10

5-16

32

81

15 / 16 / 17

TAVVKu-20

M20

1/2”

G1/2

5,5-14

10-17

32

87

15 / 16 / 17

TAVVKu-20/u

M20

1/2”

G3/4

5,5-14

10-19

36

87

15 / 16 / 17

TAVVKu-25

M25

3/4”

G3/4

8-18

15-22

36

87

15 / 16 / 17

TAVVKu-25/u

M25

3/4”

G1

8-18

15-24

42

87

15 / 16 / 17

TAVVKu-32

M32

1”

G1

13-24

20-28

42

106

15 / 20,5 / 21

TAVVKu-32/u

M32

1”

G1 1/4

13-24

20-31

48

106

15 / 20,5 / 21

TAVVKu-40

M40

1 1/4”

G1 1/4

21-30

26-37

48

106

15 / 20,5 / 21

TAVVKu-40/u

M40

1 1/4”

G1 1/2

21-30

26-37

55

106

15 / 20,5 / 21

TAVVKu-50

M50

1 1/2”

G1 1/2

24-36

31-43

55

106

15 / 20,5 / 21

TAVVKu-50/u

M50

1 1/2”

G2

24-36

31-43

68

106

15 / 20,5 / 21

TAVVKu-63

M63

2”

G2

36-45

42-53

68

106

15 / 20,5 / 21

TAVVKu-63/u

M63

2”

G2 1/2

36-45

42-53

76

106

15 / 20,5 / 21

*Cable glands for other cable and armour diameters, as well as with alternative thread types, are available on request.

Order

EXEL Х1 VVK Х2 Х3 – Х4 – Х5 where

EXEL А VVK u N 20 M20х1.5
  Х1 Х2 Х3 Х4 Х5

Here:

 Х1 – entering cable type: non-armoured (default, no marking), "TA" – armoured conduit connection;

VVK – product designation: "VVK" – explosion-proof cable glands;

Х2 – design of the gland sealing ring (u – set of O-rings);

Х3 – gland material: nickel-plated brass (default, no marking), N – stainless steel, L – bare brass, S – steel, SO – galvanized steel, A – aluminium. Similar materials may also be used;

Х4 – cable gland size;

Х5 – entry thread (metric thread M is indicated by default);

Certificates