Explosion-Proof Lamps

LVE-2 explosion-proof lamps are intended for use in low-voltage electrical circuits in combination with explosion-proof enclosures, for indoor or outdoor installation, as well as on offshore platforms and port terminals, in hazardous areas with explosive atmospheres or combustible dust.

Order

Table 2. LVE-2 Technical Parameters

Parameter LVE-2 Value
1 Enclosure Protection Rating (IP) according to GOST 14254-2015:    
1,1 not installed in the enclosure IP 20
1,2 installed in the enclosure IP 67
2 Operating Temperature, °C from -60 to +60
  Relative Humidity 100% at +25°C
3 Explosion Protection Markings:    
3,1 Gas Markings: Ex e mb IIC Gb U
3,3 Dust markings: Ex tb IIIC Db U
4 Rated Operating Voltage Ue, V АС 110-250 50/60 Hz or
DC 12-48
5 Max. Lamp Power, W 1
6 Min. Duration of Lighting, hrs 40 000
7 Cable Cross-Section, mm2 0,75….1,5
8 Dimensions LVE-2: 60х24х24
10 Weight 58 g
Climatic Version: NF1 by default; other versions available upon request.

LVE Series

For explosion-proof lamps, LVe series:

LVE – Х1 – Х2 –Х3 –(wХ4)– Х5 – …) where

Х1 – series number 2

Х2   –   colour of the light-transmitting element;

1 – white;

2 – red;

3 – green;

4 – yellow;

5 – blue;

Х3   –   operating voltage:

 AC/DC12

AC/DC24-36

AC/DC110

AC220-380

AC/DC220

w (optional) – the symbol is added when ordering a LVE unit with a pre-installed cable;

X4 (optional) – the symbol indicates the cable length in meters when ordering a LVE

                      with a non-standard cable length (different from 1 m);

Х5 – text (by default, printed on an adhesive thermal label; for individual orders — on a stainless steel nameplate):

1 – (none)

2 – on

3 – off

4 – start

5 – stop

6 – auto

7 – manual

8 – fault

Other inscriptions available upon request.

* If any position such as X1, X2, etc., is not required, use “0”. If several positions at the end of the code (e.g., “options”) are not required, simply finish the code.

Certificate No. EAEU RU C-RU.НА65.В.00540/20.

Order