Explosion-Proof Stainless Steel Control Stations

KVs series control stations are made of stainless steel and are intended for cable connection and distribution, switching and control of electrical equipment, for indoor and outdoor installation, as well as on offshore platforms and port terminals, in hazardous areas with explosive atmospheres or combustible dust.

Order

Technical Specifications

Explosion Protection Markings: 
Gas Markings:1Ex de IIC T6…T4 Gb X
Dust Markings:Ex tb IIIC Т85°C… Т135°C Db X
Ingress Protection:IP66/67/68
Rated Voltage AC/DC:Pushbuttons up to 380 V AC/DC; indicator lamps up to 250 V AC and 48 V DC
Rated Current:up to 10 A
Permissible Ambient Temperature:-60 to +60ºС
Climatic Design:NF1 by default; other options (MU1, U1, W1) on request
Material:stainless steel (304L, 314L)
Default Colour:natural grey brushed metal

Certificates

Enclosure Material Number of Elements Fig. No. L, mm N, mm H, mm T, mm K, mm D, mm
KVs-3 2 1 150 150 82 112 190 10
KVs-7 4 2 150 300 82 112 340 10
KVs-8 8 3 200 300 82 160 340 10
KVs-10 16 4 300 300 121 260 340 10
KVs-17 30 5 400 500 161 360 540 10

In addition to the listed standard designs, customized explosion-proof control stations and panels can be manufactured with any number of control, signalling, and measuring devices. To place an order, please contact our Sales Department.

Detailed information about the control and signalling devices is available at the following link.

For reference, a simplified table of control and signalling devices is provided below:

Type Marking Current (A) and Voltage (B), up to Designs Colours
pushbutton KVE-2 10 А/380 V Standard / Standard with illumination / Mushroom type White, Red, Green, Yellow, Blue, Black
lamp LVE-2 АС 110-250 V
DC 12-48 V
White, Red, Green, Yellow, Blue
switch PVE 10 А/380 V Standard / With key (various circuit options available) Black

Ordering Code:

КВХ1 – Х2 – (Х3/N3) – А (Хa/Na) – В (Xb/Nb) where,

Enclosure Characteristics:

X1 – enclosure material (c – stainless steel);

Х2 – explosion-proof enclosure index (see Table).

X3/N3 – designation and quantity of devices;

Cable Gland Characteristics:

А (Хa/Na) – type and quantity of cable glands on side A (top);

В (Xb/Nb)type and quantity of cable glands on side B (bottom);

Order

For example, an explosion-proof control station made of stainless steel with external dimensions 220×120×90 mm (type KVs-14), equipped with two momentary pushbuttons (black, 1 NC + 1 NO contact) for 220 V, two selector switches with wiring diagram No. 1 for 220–380 V, and one metal gland VVKm32 for unarmoured cable mounted on the bottom side of the enclosure, is designated as follows:

Data Sheet: Appendix